Planned maintenance work on the electrical equipment of MSK‑6, machine hall No. 2 from 08-10-26 09:00 MSK to 08-10-26 12:00 MSK

Scheduled maintenance Bare Metal Pools MSK-6 Services Dedicated Servers
08-10-26 09:00 MSK · 3 hours

Updates

Scheduled

On 08.10.2026, from 09:00 to 12:00 (MSK), monthly maintenance work will be carried out on diesel generator unit No. 7 (hereinafter referred to as DG‑7), located at the following address: Ryabinovaya St., 53, building 4 (DATAPRO LLC data center). During the work, DG‑7 will be taken out of the automatic start‑up mode, followed by testing at idle and under load.
During the work period, the power supply of the MRV-7 panel, from which input No. 1 SHCHBP-2.3 is powered (socket block / PDU marked as SHCHBP-2.3. Input No. 1 of the engine room No. 2 will be carried out from the city network via an uninterruptible power supply (hereinafter UPS No. 7). The battery life of UPS No. 7 is 32 minutes, the recovery time of the regular DSU mode is 7.5 minutes.

At the same time, input No. 2 of machine room No. 2 (a block of sockets/PDUs marked as input No. 2 of the SHCHBP-2.4) will operate normally.

These operations do not imply a service interruption, but only a reduction in redundancy.

October 5, 2026 · 14:30 MSK

← Back